Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 443

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Processing operation
: Performed, : Not performed
Control
Processing operation
mode
Deviation check
MAN
AUT
CAS, CSV
Control
Processing operation
mode
Output exclusion
processing
MAN
AUT
CAS, CSV
*1 Tracking is performed when the tracking flag (TRK) is 1.
*2 In the MAN mode, SV variation rate limiter processing is not performed.
*3 An alarm (ALM) whose corresponding bit is TRUE (detected) is reset, and the alarm will not be detected.
*4 An alarm whose corresponding bit is TRUE (Valid) in the disable alarm detection (INH) is not detected.
Operation error
Error code (SD0)
Description
3402H
Input data (DVL, DVLS, SVC, PV, SV) or tag data is a subnormal number or NaN (not a number).
3403H
An overflow has occurred.
An error may occur in a function block that is used in a tag FB. For details on the error, refer to corresponding function blocks.
PV tracking
Proportional output
operation
Tracking
SV variation rate &
high/low limiter
*1
*2
*1
Output at high or low
limit of valve
opening
Time-out detection/
time-out reset
12.39 Position Proportional Output (M+M_PVAL_T_)
One-shot output for
command pulse
period
Alarm
12
*3
*4
*4
12 LOOP TAG
441