Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Setting data
■Input/output variable
Variable
Description
name
PVP
PV input (unit: %)
CASIN
Cascade SV input (unit: %)
MVN
MV output
CASOUT
Cascade MV output (unit: %)
CASOUT_T
Cascade MV output (unit: %) (With tracking) (Indirect address)
■Public variable (operation constant)
Variable
Description
name
MTD
Derivative Gain
DVLS
Large Deviation Alarm Hysteresis
PN
Reverse Action/Direct Action
SVPTN_B0
Setting Value (SV) Used
NMAX
Output Conversion High Limit
NMIN
Output Conversion Low Limit
■Public variable (others)
• Simulation processing
Variable
Description
name
SIMOUT
Simulation Output
*1 Read or write the variables using a program. They are not displayed in "FB Property" of the engineering tool.
■Tag data
For details on tag data that is read or written with this tag access FB, refer to the following.
Page 507 PIDP
10 LOOP CONTROL OPERATION
252
10.12 Position Type PID Control (Disable Tracking for primary loop/Enable Tracking from secondary loop) (M+P_PIDP_EX_)
*1
Recommended
Type
range
0 to 100[%]
Input variable
0 to 100[%]
Input variable
NMIN to NMAX
Output variable
0 to 100[%]
Output variable
0 to 100[%]
Output variable
Recommended
Initial value
range
0 to 9999
8.0
0 to 100
2.0
0: Reverse action
0
1: Direct action
TRUE: Not used
TRUE
FALSE: Used
-999999 to 999999
100.0
-999999 to 999999
0.0
Recommended
Initial value
range
NMIN to NMAX
0.0
Data type
REAL
REAL
REAL
REAL
DWORD
Set by
Data type
User
REAL
User
REAL
User
INT
User
BOOL
User
REAL
User
REAL
Set by
Data type
System
REAL