Blend Pi Control (Disable Tracking For Primary Loop) (M+P_Bpi) - Mitsubishi Electric MELSEC iQ-R Series Programming Manual

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

10.18
Blend PI Control (Disable Tracking for primary
loop) (M+P_BPI)
M+P_BPI
This FB is used when the control amount vibrates in a short period but is stable in a long period.
FBD/LD
M+P_BPI
PVP
MVD
CASIN
Applicable tag type
BPI
Control mode
MAN
■Block diagram
PVP
(%)
Engineering
CASIN
(%)
value
conversion
*
Indicates bits item.
Setting data
■Input/output variable
Variable
Description
name
PVP
PV input (unit: %)
CASIN
Cascade SV input (unit: %)
MV output (unit: %)
MVD
10 LOOP CONTROL OPERATION
286

10.18 Blend PI Control (Disable Tracking for primary loop) (M+P_BPI)

AUT
CAS
M+P_BPI
-
Inverse
engineering
value conversion
CAS
Tag data
SV
CMV
Deviation
BPI
check
operation
Disable alarm
detection
DVLA (*)
ALM
Recommended range
0 to 100[%]
0 to 100[%]
-999999 to 999999[%]
CSV
(%)
MVD
(ΔMV)
Type
Data type
Input variable
REAL
Input variable
REAL
Output variable
REAL

Advertisement

Table of Contents
loading

Table of Contents