10.26
Loop Selector (Disable Tracking for primary loop)
(M+P_SEL)
M+P_SEL
This FB selects an input value depending on the setting of the select signal and outputs the result. The input 1 and 2 are not
tracked.
FBD/LD
M+P_SEL
PVP1
MVN
PVP2
CASOUT
SELECT
Applicable tag type
SEL
Control mode
MAN
AUT
■Block diagram
PVP1
(%)
PVP2
(%)
Engineering
value
conversion
SELECT
Tag data
PV1
* Indicates bit item.
Setting data
■Input/output variable
Variable
Description
name
PVP1
PV input (unit: %)
PVP2
PV input (unit: %)
SELECT
Selection signal
MVN
Output to a module
CASOUT
Cascade output (unit: %)
CAS
M+P_SEL
Input
selection
processing
MHA(*)
PV2
PV

10.26 Loop Selector (Disable Tracking for primary loop) (M+P_SEL)

CMV
Variation rate
high/low limit
limiter
AUT,
CAS,
MAN,
CSV
CMV
Disable alarm detection
MLA(*) DMLA(*)
MV
ALM
Recommended
Type
range
0 to 100[%]
Input variable
0 to 100[%]
Input variable
TRUE: PVP2
Input variable
FALSE: PVP1
NMIN to NMAX
Output variable
0 to 100[%]
Output variable
10 LOOP CONTROL OPERATION
CSV
MVN
Output
conversion
(MV output)
CASOUT
(%)
Data type
REAL
REAL
BOOL
REAL
REAL
10