Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 345

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Public variable (operation constant)
Variable name
Description
IN_NMAX
Input High Limit
IN_NMIN
Input Low Limit
IN_HH
High Limit Range Error
IN_H
High Limit Range Error Reset
IN_L
Low Limit Range Error Reset
IN_LL
Low Limit Range Error
PID_MTD
Derivative Gain
PID_DVLS
Large Deviation Alarm Hysteresis
PID_PN
Reverse Action/Direct Action
*1
PID_TRK
Tracking Flag
PID_SVPTN_BO
Setting Value (SV) Used
PID_SVPTN_B1
Setting Value (SV) Pattern
OUT1_NMAX
Output Conversion High Limit
OUT1_NMIN
Output Conversion Low Limit
*1 When 1 (tracking is executed) is set to the tracking flag, connect CASOUT_T of the primary loop with the input variable CASIN_T.
■Public variable (others)
• Simulation processing
Variable name
Description
SIMIN
Simulation Input
SIMOUT
Simulation Output
• Control mode change processing (MCHG function)
Variable name
Description
MODEIN
Mode Change Signal
E_
Enable Mode Change
*1 Read or write the variables using a program. They are not displayed on "FB Property" of the engineering tool.
■Tag data
For details on tag data that is read or written with this tag FB, refer to the following.
Page 491 PID
Recommended range
-999999 to 999999
-999999 to 999999
-999999 to 999999
-999999 to 999999
-999999 to 999999
-999999 to 999999
0 to 9999
0 to 100
0: Reverse action
1: Direct action
0: Not executed
1: Executed
TRUE: Not used
FALSE: Used
TRUE: Not primary MV
FALSE: Primary MV
-999999 to 999999
-999999 to 999999
*1
Recommended range
NMIN to NMAX
NMIN to NMAX
Recommended range
1 to 5
1: MAN
2: AUT
3: CAS
4: CMV
5: CSV
TRUE: Execute
FALSE: Stop
12.1 Velocity Type PID Control (Enable Tracking for primary loop) (M+M_PID_T)
Initial value
Set by
Data type
100.0
User
REAL
0.0
User
REAL
102.0
User
REAL
100.0
User
REAL
0.0
User
REAL
-2.0
User
REAL
8.0
User
REAL
2.0
User
REAL
0
User
INT
0
User
INT
TRUE
User
BOOL
TRUE
User
BOOL
100.0
User
REAL
0.0
User
REAL
Initial value
Set by
Data type
0.0
User
REAL
0.0
System
REAL
Initial value
Set by
Data type
0
User
INT
FALSE
User
BOOL
12 LOOP TAG
12
343