Processing details
■Analog memory processing
This function block increases or decreases values at a fixed rate and outputs the result from the output variable OUT_.
Output (OUT_)
Output high value (d1_)
Output setting value (SETV)
Output low value (d2_)
Mode switching (Mode)
Output addition (INC_)
Output subtraction (DEC_)
Condition
Mode switching
(MODE)
FALSE (MANUAL)
TRUE (AUTO)
MODE: Mode switching
OUT_: Output value
INC_: Output addition signal
DEC_: Output subtraction signal
INCV: Output addition value
DECV: Output subtraction value
SETV: Output setting value
d1_: Output high limit value
d2_: Output low limit value
T: Execution cycle
Operation error
Error code
Description
(SD0)
3402H
Input data (MODE, INC_, DEC_, INCV, DECV, or SETV) or operation constant (d1_, d2_) is a subnormal number or NaN (not a number).
3403H
An overflow has occurred.
8 CONTROL OPERATION
136
8.10 Analog Memory (M+P_AMR)
TRUE (AUTO mode)
TRUE
(Output addition)
Output addition
Output subtraction
(INC_)
(DEC_)
TRUE
FALSE
FALSE
TRUE
TRUE
TRUE
FALSE
FALSE
Output addition value (INCV)/s
Output subtraction value (DECV)/s
TRUE
(Output subtraction)
Output (OUT_)
OUT_ = SETV
OUT_ = OUT_ + |INCV|  T
When OUT_ is more than d1_, OUT_ equals to d1_.
OUT_ = OUT_ - |DECV|  T
When OUT_ is less than d2_, OUT_ equals to d2_.
OUT_ = OUT_
t