Loop Selector (Enable Tracking for primary loop
by CASIN_T1/_T2) (M+M_SEL_T2)
M+M_SEL_T2
This FB performs loop selector combining the functions of M+P_SEL_T2 into a single FB. The primary loop of the input 1 and
2 is tracked, but tracking from the secondary loop is not performed.
FBD/LD
M+M_SEL_T2
CASIN_T1
MVN
CASIN_T2
CASOUT
SELECT
Applicable tag type
SEL
Control mode
MAN
■Block diagram
MCHG function
(M+P_MCHG)*
CASIN_T1
(%)
(Tracking)
CASIN_T2
(%)
(Tracking)
SELECT
* (M+P_ ) indicates the main structure member tag access FB which is the main component of each function.
Setting data
■Input/output variable
Variable name
Description
CASIN_T1
PV input (Unit: %) (With tracking) (Indirect address)
CASIN_T2
PV input (Unit: %) (With tracking) (Indirect address)
SELECT
Selection signal
MVN
Output to a module
CASOUT
Cascade output (Unit: %)
*1 Connect CASOUT_T of the primary loop with the input variable CASIN_T1 and CASIN_T2.
12 LOOP TAG
420

12.33 Loop Selector (Enable Tracking for primary loop by CASIN_T1/_T2) (M+M_SEL_T2)

AUT
CAS
CMV
M+M_SEL_T2
SEL function
(M+P_SEL_T2)*
Recommended range
*1
0 to 100[%]
*1
0 to 100[%]
TRUE: CASIN_T2
FALSE: CASIN_T1
SEL_NMIN to SEL_NMAX
0 to 100[%]
CSV
(MV output)
(%)
CASOUT
Type
Data type
Input variable
DWORD
Input variable
DWORD
Input variable
BOOL
Output variable
REAL
Output variable
REAL
MVN