Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 211

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Public variable (operation constant)
Variable
Description
name
MTD
Derivative Gain
DVLS
Large Deviation Alarm Hysteresis
PN
Reverse Action/Direct Action
SVPTN_B0
Setting Value (SV) Used
■Tag data
For details on tag data that is read or written with this tag access FB, refer to the following.
Page 496 2PID
Processing details
■Deviation check
This function block performs deviation check processing.
DVL
0
-DVL
DVLA
occur
Condition
DVL < |DV|
|DV|  (DVL - DVLS)
DV: Deviation (%), DVLS: Large deviation alarm hysteresis (%), DVL: Deviation limit value (%)
DVLA
DVLA
DVLA
reset
occur
reset
10.6 2-degree-of-freedom PID Control (Disable Tracking for primary loop) (M+P_2PID)
Recommended
Initial value
range
0 to 9999
8.0
0 to 100
2.0
0: Reverse action
0
1: Direct action
TRUE: Not used
TRUE
FALSE: Used
DVLS
t
DVLS
Alarm (ALM)
Large deviation (DVLA)
TRUE (Detected)
FALSE (Reset)
10 LOOP CONTROL OPERATION
Set by
Data type
User
REAL
User
REAL
User
INT
User
BOOL
209
10

Advertisement

Table of Contents
loading

Table of Contents