Operation error
Error code
Description
(SD0)
3400H
An invalid operation (such as division by zero) is performed.
3402H
Input data (INVLD, IN) or operation constant (ST_, SN, Ys, OCHG) is a subnormal number or NaN (not a number).
3403H
An overflow has occurred.
8 CONTROL OPERATION