10.20
2 position ON/OFF Control (Enable Tracking for
primary loop) (M+P_ONF2_T)
M+P_ONF2_T
This FB performs two-position (on/off) control. The primary loop can be tracked.
FBD/LD
M+P_ONF2_T
PVP
MVP
CASIN_T CASOUT
MVB
Applicable tag type
ONF2
Control mode
MAN
AUT
■Block diagram
(%)
PVP
Engineering
CASIN_T
(%)
value
(Tracking)
conversion
CAS
Tag data
Setting data
■Input/output variable
Variable
Description
name
PVP
PV input (unit: %)
CASIN_T
Cascade SV input (unit: %) (With tracking) (Indirect
address)
MVP
MV output (unit: %)
CASOUT
Cascade output (unit: %)
ON/OFF output (turns on at MV  50%)
MVB
CAS
M+P_ONF2_T
-
Tracking valid
(Operation constant
TRK=1)
Inverse
engineering
value conversion
SV
Recommended range
0 to 100[%]
0 to 100[%]
0 to 100[%]
0 to 100[%]
TRUE: On
FALSE: Off

10.20 2 position ON/OFF Control (Enable Tracking for primary loop) (M+P_ONF2_T)

CMV
MV
correction
Tracking
(primary loop)
MAN,
AUT,
AUT,
CMV
CAS,
MAN,
CSV
CMV
MV
Type
Input variable
Input variable
Output variable
Output variable
Output variable
10 LOOP CONTROL OPERATION
CSV
MVP
(%)
(%)
CASOUT
2 position
MVB
ON/OFF
control
(Bit output)
Data type
REAL
DWORD
REAL
REAL
BOOL
295