12.37
Multi-Point Program Setter (M+M_PGS2_)
M+M_PGS2_
This FB performs program settings combining the functions of M+P_PGS2_ into a single FB. Multiple FBs can be connected
to execute time width sets and setting value programs of 32 steps or more.
FBD/LD
M+M_PGS2_
PVIN
CASOUT
ADVANCE
PTNEND
INITSTART
LINKOUT
LINKIN
Applicable tag type
PGS2
Control mode
MAN
■Block diagram
MCHG function
(M+P_MCHG) *
PVIN
ADVANCE
INITSTART
LINKIN
* (M+P_ ) indicates the main structure member tag access FB which is the main component of each function.
Setting data
■Input/output variable
Variable name
Description
PVIN
Process input (Engineering value)
ADVANCE
Advance command
INITSTART
Initial start command
LINKIN
Link input (Indirect address)
CASOUT
Cascade output (Unit: %)
PTNEND
Pattern end output
LINKOUT
Link output (Indirect address)
12 LOOP TAG
428
12.37 Multi-Point Program Setter (M+M_PGS2_)
AUT
CAS
CMV
M+M_PGS2_
PGS2 function
(M+P_PGS2_) *
Recommended range
-32768 to 32767
TRUE, FALSE
TRUE, FALSE
0 to 100[%]
TRUE, FALSE
CSV
(%)
CASOUT
PTNEND
LINKOUT
Type
Data type
Input variable
REAL
Input variable
BOOL
Input variable
BOOL
Input variable
DWORD
Output variable
REAL
Output variable
BOOL
Output variable
DWORD