■Output ON time conversion/output conversion
This function block outputs a duty manipulated value (MVB) to a manipulated value (MV).
Item
Duty manipulated value (MVB) ON time
Duty manipulated value (MVB) OFF time
CTDUTY: Control output cycle, T: Execution cycle, MV: Manipulated value (%)
Ex.
Execution cycle: T = 100ms, Control output cycle: CTDUTY = 1.0s, Manipulated value: MV = 30%
MV read
Execution
cycle (ΔT)
100ms
Control
output cycle
(CTDUTY)
ON
manipulated
variable (MV) 30%
ON: 300ms
■Disable alarm detection
This function block sets whether to detect alarms (ALM) or not in the variation rate & high/low limiter processing.
Item
Disable alarm detection by setting tag data
Disable alarm detection by control mode selection
Disable alarm detection by loop stop processing
■Hold processing
This function block sets whether to hold M+P_DUTY outputs or not when a sensor error (SEA) has occurred in M+P_IN, a tag
access FB.
The hold processing is set in the process control extended setting in the engineering tool.
[Options] [Convert] [Process Control Extension Setting] [I/O Control] [Holding Processing]
• "Yes" is selected for "Hold the output of M+P_OUT1, M+P_OUT2, M+P_DUTY"; Outputs are held.
• "No" is selected for "Hold the output of M+P_OUT1, M+P_OUT2, M+P_DUTY"; The operation continues.
■Loop stop processing
When the stop alarm (SPA) of the alarm (ALM) is TRUE, this function block performs the following processing.
• Outputs (MVB) are held.
• The control mode is automatically switched to MANUAL.
• When DMLA, MHA, or MLA of the alarm (ALM) has occurred, the DMLA, MHA, or MLA is reset.
• No alarm is detected in the variation rate & high/low limiter processing.
Description
Duty manipulated value (MVB) ON time = ON time execution cycle count T
The ON time execution cycle count is defined as the following value with the first digit after the decimal point
rounded off.
CTDUTY×MV
ΔT×100
Duty manipulated value (MVB) OFF time = OFF time execution cycle count T
The OFF time execution cycle count is defined as (number of executions in a control output cycle) - (execution
cycle count of ON time).
1s
OFF: 700ms
Disable alarm detection processing
If the following bits in the disable alarm detection (INH) are TRUE, no DMLA,
MHA, or MLA of the alarm (ALM) will be detected.
• ERRI
• DMLI
• MHI
• MLI
In MAN or CMV mode, DMLA, MHA, and MLA of the alarm (ALM) are reset
and DMLA, MHA, or MLA will not be detected.
Page 171 Loop stop processing
MV read
1s
ON
ON: 300ms
OFF: 700ms