Setting data
■Input/output variable
Variable name
Description
PVP
PV input (unit: %)
CASIN
Cascade SV input (unit: %)
MV output (unit: %)
MVD
CASDR_MVOUT
MV output for cascade direct (Unit: %)
■Public variable (operation constant)
Variable
Description
name
MTD
Derivative Gain
DVLS
Large Deviation Alarm Hysteresis
PN
Reverse Action/Direct Action
SVPTN_B0
Setting Value (SV) Used
PVTRK_EN
PV Tracking Execution condition
ISTP
Integration Stop Signal
DSTP
Derivation Stop Signal
LMT_ISTP
Stop Integration, when MV variation rate limiter alarm
occurred
SVLMT_EN
SV High/Low Limiter
■Tag data
For details on tag data that is read or written with this tag access FB, refer to the following.
Page 501 2PIDH
Processing details
■Deviation check
This function block performs deviation check processing.
DVL
0
-DVL
DVLA
occur
Condition
DVL < |DV|
|DV|  (DVL - DVLS)
DV: Deviation (%), DVLS: Large deviation alarm hysteresis (%), DVL: Deviation limit value (%)
DVLA
DVLA
reset
occur
10.8 2-degree-of-freedom Advanced PID Control (Disable Tracking for primary loop) (M+P_2PIDH_)
Recommended
Type
range
0 to 100[%]
Input variable
0 to 100[%]
Input variable
-999999 to 999999[%]
Output variable
0 to 100[%]
Output variable
Recommended
Initial value
range
0 to 9999
8.0
0 to 100
2.0
0: Reverse action
0
1: Direct action
TRUE: Not used
TRUE
FALSE: Used
TRUE: Execute
FALSE
FALSE: Stop
TRUE: Execute
FALSE
FALSE: Stop
TRUE: Execute
FALSE
FALSE: Stop
TRUE: Stop
FALSE
FALSE: Not stop
TRUE: Executed
FALSE
FALSE: Not executed
DVLS
t
DVLS
DVLA
reset
Alarm (ALM)
Large deviation (DVLA)
TRUE (Detected)
FALSE (Reset)
Data type
REAL
REAL
REAL
REAL
Set by
Data type
User
REAL
User
REAL
User
INT
User
BOOL
User
BOOL
User
BOOL
User
BOOL
User
BOOL
User
BOOL
10 LOOP CONTROL OPERATION