Parameter Window Active Power Total - ABB i-bus KNX Product Manual

Energy actuator se/s 3.16.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
3.2.3.2

Parameter window Active power total

In parameter window Active power total, the parameters and communication objects for recording and
monitoring of the Active power total (sum of outputs A, B and C) are enabled. The parameter window is
enabled when in parameter window Function, page 35, the parameter Monitor "Active power total" has
been selected with the option yes.
Send "Active power" after a change
Options:
yes: The value of the communication object Active power (Active power total) is sent on a change.
The following parameter appears:
Send "Active power" on request
Options:
yes: The value of the communication object Active power (Active power total) is sent when a telegram
is received on the communication object Request power values. This communication object is enabled
in the parameter window General, page 29 .
Send "Active power" cyclically
Options:
yes: The communication object Active power (Active power total) is sent cyclically. The setting of the
cycle time is undertaken in parameter window General, page 29 (parameter Cycle time for power val-
ues).
Cycle time and request objects are set
on "General"
<−−− NOTE
42 2CDC 505 084 D0203 | SE/S 3.16.1
no
yes
Send "Active power" when
+/- W [1...13,800]
Options:
1...20...13,800
This parameter determines which changes of the value of the communication object Active power
are sent.
no
yes
no
yes