Parameter Window Metering (Wh) - ABB i-bus KNX Product Manual

Energy actuator se/s 3.16.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
3.2.2

Parameter window Metering (Wh)

In parameter window Metering (Wh), the higher-level settings that apply for all meters are undertaken, and
the Meter reading total can be enabled here with the respective parameter window.
Enable communication object
"Request meter readings" 1 bit
Options:
yes: A 1 bit communication object Request meter readings is enabled. Using this communication ob-
ject, all meter readings can be requested, provided that the meters have been enabled and they have
been parameterized with the option on request.
Meter total Meter reading
Intermediate meter total Meter reading
Meter Meter reading Output A...C
Intermediate meter Meter reading Output A...C
With the option yes, the following parameters appear:
no
yes
Request with object value
Options:
0
1
0 or 1
0: Sending status messages is requested with the value 0.
1: Sending status messages is requested with the value 1.
0 or 1: Sending status messages is requested with the value 0 or 1.
SE/S 3.16.1 | 2CDC 505 084 D0203 33