Product and functional overview

The ABB i-bus
4 space units in Pro M design for installation in a distribution board.
The connection to the ABB i-bus KNX is established using the front side bus connection terminal. The
assignment of the physical addresses as well as the parameterization is carried out with Engineering Tool
Software ETS from version ETS3.0f.
The Energy Actuator can switch three independent electrical AC current loads or one three-phase current
load via KNX using floating contacts. The outputs can be manually switched on and off. The switching
states are displayed.
Important
The Energy Actuator cannot guarantee precise simultaneous switching of all three outputs. For this
reason, the SE/S is not suitable, for example, for switching three-phase motors as they would be de-
stroyed by the voltage peaks that occur.
The device is especially suitable for switching loads with high peak inrush currents such as lighting equip-
ment with compensation capacitors or fluorescent lamp loads (AX) to EN 60669.
The following functions are available:
Recording of the active consumption with a main meter and a flexibly programmable intermediate me-
ter for each output. The intermediate meter can be started and stopped in dependence on defined
events (1 bit telegrams, time, and consumption). Warnings can be sent on the KNX or the output can
be switched depending on these events.
Current, voltage, active power and frequency can be recorded and monitored with the aid of threshold
values. Warnings can be sent on the KNX or the output can be switched depending on these events.
The recording of apparent power, power factor and crest factor are also available.
A simple load control can be implemented. Every Energy Actuator can be configured as a master, and
the total power of a system by up to ten further Energy Actuators can be recorded. Load shedding
stages are sent on the bus, and the devices are shutdown according to their own load shedding stage.
Function Time: Staircase lighting, switch ON and OFF delay and flashing
Recall 8 bit scenes
Logical functions AND, OR, XOR and GATE
Functions forced operation and safety
Selection of the default position at bus voltage failure and bus voltage recovery
Individual outputs can be copied or exchanged to reduce the programming effort.
®
KNX Energy Actuator SE/S 3.16.1 is a modular installation device with module widths of
SE/S 3.16.1 | 2CDC 505 084 D0203 5