Communication objects Meter total

No.
31
This communication object is enabled if in parameter window
total" has been selected with the option yes.
The value of the communication object is calculated from the sum of the meter outputs A...C. The Meter total can only be
reset via communication objects no. 11 and 12.
3.3.5

Communication objects Intermediate meter total

Note
The functions of communication objects No. 34 and 35 change in accordance with the parameterization.
No.
32
This communication object is enabled if in parameter window
total" has been selected with the option yes.
The Intermediate meter total is derived from the Meter total. It is controlled via communication objects no. 33...36.
33
This communication object is enabled if in parameter window
total" has been selected with the option yes.
The value of the communication object is sent when a telegram is received on the communication object Request status
values.
This communication object indicates whether the counter is currently started or stopped and whether the meter reading could
be erroneous. This can be the case, for example, during a start or stop event if bus voltage is not available and this event is
thus not recorded.
Telegram value:
Bit 0:
Bit 1:
Bit 2...7:
34
This communication object is enabled if in parameter window
(Start) is activated by has been selected by the option 1 bit object.
The intermediate meter starts if a telegram with the value 1 is received via this communication object. You can parameterize
whether the intermediate readings are reset and/or sent.
104 2CDC 505 084 D0203 | SE/S 3.16.1
Function
Meter reading
Function
Meter reading
Status
1 = meter reading is started
0 = meter reading is stopped
1 = since the last reset of the intermediate meter, a bus voltage failure or download has occurred. The
meter reading may not be correct.
0 = since the last reset of the intermediate meter, no bus voltage failure or download has occurred.
Not assigned, 0.
Receive trigger 1
Object name
Meter total
Metering
(Wh), page 33, the parameter Enable "Meter reading
Object name
Intermediate meter total
Metering
(Wh), page 33, the parameter Enable "Meter reading
Intermediate meter total
Metering
(Wh), page 33, the parameter Enable "Meter reading
Intermediate meter total
Meter reading total
(Wh), page 38, the parameter Trigger 1
Data type
Flags
4 byte
C, R, T
DPT 13.010
Data type
Flags
4 byte
C, R, T
DPT 13.010
1 byte
C, R, T
non DPT
1 bit
C, W
DPT 1.017