Commissioning
3.2.5.9

Parameter window A: Load control slave

In parameter window Load control slave, the behaviour of the output is parameterized, provided that the
output is used as a slave for load control. The master can be another Energy Actuator, the device itself or
e.g. another visualization.
Load shedding stage output [1...8]
Options:
Can be separately parameterized for each output at which shedding stage the output is switched off.
Should the Energy Actuator receive a shedding stage on the communication object Receive load shedding
stage that is greater than or equal to the Load shedding stage output, the output will then switch off. If the
received shedding stage is less than the parameterized Load shedding stage output, the output is re-
enabled.
Load shedding stage can be changed
via object
Options:
yes: The shedding stage of the output (communication object Shedding stage) can be modified via the
bus. The following parameter appears:
Slave is controlled via
Options:
external object: The shedding stage is received via the bus, the Energy Actuator is not the master.
Receives load shedding stage internally: The Energy Actuator generates the shedding stage itself; it is
also the master. The communication object Receive load shedding stage is not required and can be
made invisible (in parameter window Function, page 35). The shedding stage is transferred internally
to the output.
Enable object "Receive load
shedding stage" on "Function"
<−−− NOTE
90 2CDC 505 084 D0203 | SE/S 3.16.1
1...8
no
yes
Overwrite load shedding stage with
download or ETS reset
Options:
yes
no
yes: The shedding stage modified via the bus is overwritten after a download or ETS reset.
external object:
receives load shedding stage internally