ABB i-bus KNX Product Manual page 78

Energy actuator se/s 3.16.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
Stop "Intermediate meter reading"
on trigger 2
Options:
Note
This parameter is not available should Limit be selected beforehand. Instead of the parameter Reaction
to stop, the parameter Contact position when limit is reached appears with the same options as in
parameter Reaction to stop.
no: The intermediate meter sends its meter reading at trigger 2 and continues to count further (without
reset).
yes: The intermediate counter sends its meter reading at trigger 2 and must be restarted by trigger 1.
The following parameter appears:
"Intermediate meter reading"
additionally resettable via object
Options:
yes: The communication object Reset (A: Intermediate meter) is enabled. When a telegram is re-
ceived with the value 1 on the communication object, the meter reading is sent and subsequently re-
set to zero. The status of the meter is not changed, i.e. if the meter is metering, it will continue to take
readings; if it is stopped, it will remain stopped.
Overwrite start-, stop time, duration
and limit with download or ETS reset
Options:
yes: After a download or ETS reset, the values changed on the bus are overwritten again with the pa-
rameter values.
no: After a download or ETS reset, the values changed on the bus are retained.
76 2CDC 505 084 D0203 | SE/S 3.16.1
yes
no
Reaction to stop
Options:
no reaction
switch ON until next switch operation
switch OFF until next switch operation
If the intermediate meter is stopped at trigger 2, the output can switch on, switch off or retain its
switch position. The switching is evaluated as a "normal" switch telegram, i.e., the output is not in-
hibited and every new switch telegram can switch the output again.
no
yes
no
yes