ABB i-bus KNX Product Manual page 142

Energy actuator se/s 3.16.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Planning and application
Behaviour with:
Communication object
Permanent ON
Scenes
Logic (communication
object Logical connection
x)
Forced operation
Load control slave (Output A...C)
Behaviour with:
Communication objects:
Load shedding stage
output X
Communication object:
Deactivate load control
140 2CDC 505 084 D0203 | SE/S 3.16.1
Bus voltage recovery
Download
The value is retained. If
If Permanent ON has not
Permanent ON was active
been assigned to a group
before bus voltage failure,
address, Permanent ON
Permanent ON will be
remains off. Otherwise the
reactivated after bus
state of Permanent ON
voltage recovery.
remains unchanged.
The scene values saved in
Overwriting of the scene
the actuator are restored.
values can be parameter-
ized (parameter window X:
The values of the CO
Function).
Scenes are lost. If an
output has been switched
The values of the CO
via Scene, it will be reset if
Scenes are lost.
necessary.
Programmable
If Logical connection x has
not been assigned to a
(Parameter window
group address, the
X: Logic)
corresponding connections
are without function.
Otherwise the values of
Logical connection x are
retained. However, an
evaluation is performed
only after the next event.
Programmable
If Forced operation has not
been assigned to a group
(Parameter window
address, the Forced
X: Safety)
operation remains inactive.
Otherwise, the value of
Forced operation is
retained.
Bus voltage recovery
Download
Is retained.
A parameter decides
whether the values in the
parameters are accepted.
The response can be
Is retained.
parameterized
active
not active
unchanged
ETS reset
Full download / applica-
tion update
Permanent ON is no longer
As with ETS reset
active.
As with download
The scene values are
overwritten with the
parameterized scene
assignments.
As with bus voltage
As with bus voltage
recovery
recovery
As with bus voltage
As with bus voltage
recovery
recovery
ETS reset
Full download / applica-
tion update
As with download
Parameters are accepted.
Is set to the value 0.
Is set to the value 0.