ABB i-bus KNX Product Manual page 66

Energy actuator se/s 3.16.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
Flash if object "Switch" is
Options:
Here you set the value of the communication object Switch, at which the output flashes. Flashing is not
retriggerable.
1: Flashing starts when a telegram with the value 1 is received on the communication object Switch. A
telegram with the value 0 ends flashing.
0: Flashing starts when a telegram with the value 0 is received on the communication object Switch. A
telegram with the value 1 ends flashing.
1 or 0: A telegram with the value 1 or 0 triggers flashing. Suspension of flashing is not possible in this
case.
Time for ON in sec [0...65,535]
Options:
This time for ON defines how long the output is switched ON during a flashing period. The smallest value
is 1 second.
Note
Only a certain number of switching actions are possible per minute and Energy Actuator. With frequent
switching, a switching delay can occur, as only a certain number of switching actions are possible per
minute, see
Time for OFF in sec [0...65,535]
Options:
This time for OFF defines how long the output is switched ON during a flashing period. The smallest value
is 1 second.
Note
Only a certain number of switching actions are possible per minute and Energy Actuator. With frequent
switching, a switching delay can occur, as only a certain number of switching actions are possible per
minute, see
64 2CDC 505 084 D0203 | SE/S 3.16.1
1
0
1 or 0
0....5...65,535
Technical
data, page 7. The same applies directly after bus voltage recovery.
0....5...65,535
Technical
data, page 7. The same applies directly after bus voltage recovery.

Advertisement

Table of Contents
loading