Short Overview Of The Communication Objects - ABB i-bus KNX Product Manual

Energy actuator se/s 3.16.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
3.3.1

Short overview of the communication objects

CO*
Function
No.
0
In operation
1
Safety priority 1
2
Safety priority 2
3
Safety priority 3
4
Request status values
5
Request meter readings
6
Request instrument values
7
Request power values
8
Receive time
9
Measurement circuit active
10
Receive load shedding stage
11
Enable reset meters
12
Reset meter readings
13
Deactivate load control
15
Status load control
16
Load limit exceeded
17
Receive power value 1
18
Receive power value 2
19
Receive power value 3
20
Receive power value 4
21
Receive power value 5
22
Receive power value 6
23
Receive power value 7
24
Receive power value 8
25
Receive power value 9
26
Receive power value 10
27
Send sum power values
28
Send load shedding stage
29
Choose load limit
Send load limit
30
Receive/send load limit
31
Meter reading
* CO = communication object
Name
System
General
General
General
General
General
General
General
General
Diagnostics
Load control
Meter reading
Meter reading
Load control master
Load control master
Load control master
Load control master
Load control master
Load control master
Load control master
Load control master
Load control master
Load control master
Load control master
Load control master
Load control master
Load control master
Load control master
Load control master
Load control master
Load control master
Meter total
Flags
Data Point
Length
Type (DPT)
C
DPT 1.002
1 bit
x
DPT 1.005
1 bit
x
DPT 1.005
1 bit
x
DPT 1.005
1 bit
x
DPT 1.017
1 bit
x
DPT 1.017
1 bit
x
DPT 1.017
1 bit
x
DPT 1.017
1 bit
x
DPT 10.001
3 byte
x
DPT 1.011
1 bit
x
DPT 236.001
1 byte
x
DPT 1.003
1 bit
x
DPT 1.015
1 bit
x
DPT 1.003
1 bit
x
DPT 27.001
4 byte
x
DPT 1.005
1 bit
x
DPT 14.056
4 byte
x
DPT 14.056
4 byte
x
DPT 14.056
4 byte
x
DPT 14.056
4 byte
x
DPT 14.056
4 byte
x
DPT 14.056
4 byte
x
DPT 14.056
4 byte
x
DPT 14.056
4 byte
x
DPT 14.056
4 byte
x
DPT 14.056
4 byte
x
DPT 14.056
4 byte
x
DPT 236.001
1 byte
x
DPT 5.010
1 byte
x
DPT 14.056
4 byte
x
DPT 14.056
4 byte
x
DPT 13.010
4 byte
x
SE/S 3.16.1 | 2CDC 505 084 D0203 93
R
W
T
A
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

Advertisement

Table of Contents
loading

Table of Contents