Parameter window Load control master

In the parameter window Load control master, the settings for the load control are undertaken, provided
that the Energy Actuator is used as a master for load control. The parameter window is enabled when in
parameter window Function, page 35, the parameter Device is load control master has been selected with
the option yes.
Number of load shedding stages [1...8]
Options:
The slaves assigned to the master are assigned depending on the priority of the load shedding stage. If
the parameterized load limit is exceeded, the master sends load shedding stages on the bus. The load
shedding stage is increased, commencing at load shedding stage 1, until the load limit is no longer ex-
ceeded. If the load limit is exceeded, the load shedding limit is reduced again.
Load limit can be changed
Options:
yes, 4 values selectable: The communication objects Choose load limit and Send load limit are ena-
bled. Using communication object Choose load limit, you can choose between four parameterized
load limits. The following parameters appear:
46 2CDC 505 084 D0203 | SE/S 3.16.1
1...2...8
yes, 4 values selectable
yes, object writable