KNX
Commissioning
Contact position when
exceeding upper limit
Options:
no reaction
switch OFF until next switch operation
switch ON until next switch operation
switch OFF until value is falling below threshold again
switch ON until value is falling below limit again
switch ON/OFF until next switch operation: The output switches after threshold value 1 is ex-
ceeded, and the parameterized Delay for switching has timed out. The switching is evaluated
as a "normal" switch telegram, i.e., the output is not inhibited and every new switch telegram
can switch the output again.
switch OFF/ON until value is falling below threshold again: The output switches after threshold
value 1 is exceeded, and the parameterized Delay for switching has timed out. Normal switch-
ing can occur again only after the value has fallen below the threshold again. Exception: A tel-
egram with a higher priority, see
Enable threshold 2
Options:
no
yes
Parameterization of threshold value 2 is identical to threshold value 1.
function
diagram, page 120.