ABB i-bus
KNX
Commissioning
No.
78
This communication object is enabled if in parameter window
by has been selected with the option Time.
The parameterized stop time can be modified using this communication object.
If the parameterized stop time is received via the communication object Receive time (no. 8), the intermediate meter reading is
sent. You can parameterize whether the intermediate meter stops or continues to count, or whether the output switches at
stop when trigger 2 is received.
78
This communication object is enabled if in parameter window
by has been selected with the option Limit.
The parameterized limit can be modified using this communication object.
If the parameterized limit is reached, the intermediate meter reading is sent and the intermediate meter stops. It is possible to
parameterize whether the output stops when switched.
78
This communication object is enabled if in parameter window
by has been selected with the option Duration.
The parameterized duration can be modified using this communication object.
The intermediate meter reading is sent when the parameterized duration is reached. You can parameterize whether the
intermediate meter stops or continues to count, or whether the output switches at stop when trigger 2 is received.
79
This communication object is enabled if in parameter window
reading total" additionally resettable via object by has been selected with the option yes.
The intermediate meter is reset if a telegram with the value 1 is received via this communication object.
Function
Trigger 2 change time
Trigger 2 change limit
Trigger 2 change duration
Reset
Object name
A: Intermediate meter
A: Metering
(Wh), page 73, the parameter Trigger 2 is activated
A: Intermediate meter
A: Metering
(Wh), page 73, the parameter Trigger 2 is activated
A: Intermediate meter
A: Metering
(Wh), page 73, the parameter Trigger 2 is activated
A: Intermediate meter
A: Metering
(Wh), page 73, the parameter "Intermediate meter
Data type
Flags
3 byte
C, R, W, T
DPT 10.001
4 byte
C, R, W, T
DPT 13.010
2 byte
C, R, W, T
DPT 7.006
1 bit
C, W
DPT 1.015
SE/S 3.16.1 | 2CDC 505 084 D0203 113