Communications Objects A: Instrument And Power Values - ABB i-bus KNX Product Manual

Energy actuator se/s 3.16.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
3.3.8.4

Communications objects A: Instrument and power values

No.
82
This communication object is enabled if in parameter window
active power has been selected with the option yes.
The value of the communication object is sent in Watts on the bus.
If the active power is negative (power feed), the value of the communication object can be issued, but not monitored by
threshold values (only positive threshold values).
83
This communication object is enabled if in parameter window
thresholds has been selected with the option yes.
Threshold 1 lower limit and Threshold 1 upper limit are the hysteresis limits of threshold value 1. If the value falls below the
lower limit or exceeds the upper limit, a parameterized reaction occurs (warning is sent).
84
See communication object 83.
85
This communication object is enabled if in parameter window
thresholds has been selected with the option yes.
The warning is sent with the parameterized value if threshold value 1 is exceeded or fallen below.
86
See Threshold value 1.
87
See Threshold value 1.
88
See Threshold value 1.
89
This communication object is enabled if in parameter window
current has been selected with the option yes.
The value of the communication object is sent in Ampere on the bus.
Function
Active power
Threshold 1 lower limit
Threshold 1 upper limit
Threshold 1 warning
Threshold 2 lower limit
Threshold 2 upper limit
Threshold 2 warning
Current Value
Object name
A: Active power
A: Instrument and power
A: Active power
A: Monitor active
power, page 80, the parameter Enable
A: Active power
A: Active power
A: Monitor active
power, page 80, the parameter Enable
A: Active power
A: Active power
A: Active power
A: Current
A: Instrument and power
Data type
Flags
4 Byte
C, R, T
DPT 14.056
values, page 77, the parameter Monitor
4 Byte
C, R, W, T
DPT 14.056
4 Byte
C, R, W, T
DPT 14.056
1 bit
C, R, T
DPT 1.005
4 Byte
C, R, W, T
DPT 14.056
4 Byte
C, R, W, T
DPT 14.056
1 bit
C, R, T
DPT 1.005
4 Byte
C, R, T
DPT 14.019
values, page 77, the parameter Monitor
SE/S 3.16.1 | 2CDC 505 084 D0203 115

Advertisement

Table of Contents
loading