Commissioning
3.2.1

Parameter window General

In this parameter window, the main parameter settings relevant for the entire DALI Light Controller are
undertaken.
Use copy function to copy or exchange
light groups.
(right mouse click on device
in ETS-Topologie)
<−−− NOTE
Enable automatic DALI addressing
Options:
Using this parameter, the automatic DALI addressing process of the DLR/A can be switched off.
yes: The DLR/A automatically performs a DALI addressing assignment. If the DLR/A locates a DALI
device without DALI address assignment, it automatically allocates the first free DALI address to the
DALI device.
40 2CDC507128D0202 | DLR/A 4.8.1.1