ABB i-bus
KNX
Commissioning
Enable object "Crest factor"
Options:
•
yes: The communication object Crest factor (A: Crest factor current) is enabled. The following parame-
ters appear:
Cycle time and request objects are set
on "General"
<−−− NOTE
Send "Power factor" cyclically
Options:
no
yes
•
yes: The value of the communication object Power factor is sent cyclically. The setting of the
cycle time is undertaken in parameter window General, page 29 (parameter Cycle time for in-
strument values).
no
yes
Send "Crest factor" after a change
Options:
no
yes
•
yes: The value of the communication object Power factor (A: Crest factor) is sent in the event
of a change. The following parameter appears:
Send "Crest factor" when
+/- 0.1 x value [1...100]
Options:
1...5...100
This parameter determines which changes of the value of the communication object Crest
factor current are sent.
Send "Crest factor" on request
Options:
no
yes
•
yes: The value of the communication object Crest factor current is sent when a telegram is re-
ceived on the communication object Request instrument values. This communication object is
enabled in the parameter window General, page 29 .
Send "Crest factor" cyclically
Options:
no
yes
•
yes: The value of the communication object Crest factor current is sent cyclically. The setting of
the cycle time is undertaken in parameter window General, page 29 (parameter Cycle time for
instrument values).
SE/S 3.16.1 | 2CDC 505 084 D0203 79