Programming
Type
Function
Selection
OUTPUT PT
AUX CONST
NOTIF
AUX RESET
AUX DOOR
OUTPUT PT
AUX RESET
RELAY
AUX DOOR
W-Gateway
W-SWITCH
Same as SWITCH
W-Relay
Same as Relay
8.5.2 Point Programming for the Internal or External Power Module
To program for an internal or external power module points, follow these steps:
1.
Login to the panel.
2.
Select 7 to access the Program Menu.
3.
Press 4 to enter the Point Menu.
4.
Press the up or down arrows to select the desired module. Press ENTER. Refer to Section 7.5 for the available choices.
5.
Enter the number of the circuit or point you want to edit. Refer to the table below for available selections.
6.
Press ENTER.
7.
To select the Type, press the up or down arrows, then, press ENTER.
8.
To select the Function, press the up or down arrows, then, press ENTER.
9.
To select the Group, press the up or down arrows, then, press ENTER.
10. To edit the Point Name, press the right arrow to skip Point Name Edit. See Section 8.5.
11. Repeat steps 1 through 10 for all circuits.
86
Latching
Option
Select Group
Output Point, a general use notification type. Use for driving standard notification
appliances.
Use constant power for applications that require a constant auxiliary power source. Power
is always present at Constant circuits.
Use for auxiliary power, resettable applications. See "Resettable Power" on page 50 to
learn how this option operates.
Use for auxiliary power, door holder applications. For example, if you were using an
auxiliary power supply for door holders, you would use this option. See "Door Holder
Power" on page 50 to learn how this option operates.
Select Group
Output Point, a general use relay type. Use for applications requiring a relay, such as
elevator recall.
Use for auxiliary power, resettable applications. See "Resettable Power" on page 50 to
learn how this option operates.
Use for auxiliary power, door holder applications. For example, if you were using an
auxiliary power supply for door holders, you would use this option. See "Door Holder
Power" on page 50 for a description of how this option operates.
Wireless Gateway
Table 8.4 Point Programming for Internal SLC Module (Continued)
Comments
IFP-75 Series Manual — P/N LS10147-001SK-E:E 4/6/2022