13. OPTIONS AND AUXILIARY EQUIPMENT
13.2.4 Relays
The following relays should be used with the interfaces:
Input signals (interface DI-1) signals
Relay used for digital output signals (interface DO-1)
13.2.5 Surge absorbers
www.DataSheet4U.com
A surge absorber is required for the electromagnetic brake. Use the following surge absorber or equivalent.
Insulate the wiring as shown in the diagram.
Permissible circuit
voltage
AC[Vma]
DC[V]
140
Note: 1 time
8
13.2.6 Noise reduction techniques
Noises are classified into external noises which enter the servo amplifier to cause it to malfunction and
those radiated by the servo amplifier to cause peripheral devices to malfunction. Since the servo amplifier
is an electronic device which handles small signals, the following general noise reduction techniques are
required.
Also, the servo amplifier can be a source of noise as its outputs are chopped by high carrier frequencies. If
peripheral devices malfunction due to noises produced by the servo amplifier, noise suppression measures
must be taken. The measures will vary slightly with the routes of noise transmission.
(1) Noise reduction techniques
(a) General reduction techniques
Avoid laying power lines (input and output cables) and signal cables side by side or do not bundle
them together. Separate power lines from signal cables.
Use shielded, twisted pair cables for connection with the encoder and for control signal
transmission, and connect the shield to the SD terminal.
Ground the servo amplifier, servo motor, etc. together at one point (refer to Section 3.10).
Interface
Maximum rating
Surge
Energy
immunity
immunity
[A]
[J]
(Note)
180
5
500/time
20 s
(Example) ERZV10D221 (Matsushita Electric Industry)
TNR-10V221K (Nippon chemi-con)
Outline drawing [mm] ( [in] ) (ERZ-C10DK221)
13.5 (0.53)
0.8 (0.03)
Selection example
To prevent defective contacts , use a relay for small signal
(twin contacts).
(Ex.) Omron : type G2A , MY
Small relay with 12VDC or 24VDC of 40mA or less
(Ex.) Omron : type MY
Static
Maximum
capacity
Rated
limit voltage
(reference
power
value)
[W]
[A]
[V]
0.4
25
360
4.7 1.0 (0.19 0.04)
13 - 24
Varistor voltage
rating (range) V1mA
[pF]
[V]
220
300
(198 to 242)
Vinyl tube
Crimping terminal
for M4 screw