Error
Error name
code
4133H
File related error
4134H
File related error
4136H
File related error
4137H
File related error
4138H
File related error
4139H
File related error
413AH
File related error
413EH
File related error
413FH
File related error
414AH
Intelligent function
module specification
error
414CH
Intelligent function
module specification
error
4150H
File related error
4151H
File related error
41C5H
File related error
41F8H
File related error
41FBH
File related error
41FDH
File related error
4269H
Other error
433CH
Maintenance related
error
433DH
Maintenance related
error
4A00H
Network related error
33 ERROR CODE LIST
252
33.2 Other Error Codes
Error details and cause
• The specified device (memory) has no free space.
• The attribute specification data for a file is incorrect.
• The specified file already exists.
• The specified file is read-only.
• Simultaneously accessible files exceeded the
maximum.
• The specified file exceeded the file size range of the
file already exists.
• The specified file exceeded the file size of the file
already exists.
• Operation is disabled for the specified drive (memory).
• Writing to the file storage area is prohibited for the file.
• Operation was performed to the intelligent function
module outside of the control group in a multiple CPU
system.
• Inaccessible buffer memory address was specified.
• An attempt was made to initialize the drive protected
by the system.
• An attempt was made to delete the file/folder protected
by the system.
• The specified file does not exist.
• An attempt was made to write data to a read-only file.
• The same data is being accessed with another
engineering tool.
• The specified file has been operated with the same
engineering tool.
• Data is not written to the data memory.
• The remote Y OUT or remote RUN operation cannot
be performed.
• Clearing error failed. (The error clear function has been
performed while an error is being cleared.)
• The target module does not support the error clear
function.
• The specified network number and station number are
incorrect.
• The specified station cannot be accessed because the
routing parameters have not been set to the start
source CPU and the relay CPU module.
• The control CPU module for the network module to
which data is routed has not started for routing via a
multiple CPU system.
• The CPU module that relays IP packets is not the
control CPU module for the CC-Link IE module on the
path where IP packets travel.
Corrective action
• Increase the free space of the drive (memory), and
execute the request again.
• Check the specified data, and execute the request
again.
• Check the specified file name, and execute the request
again.
• Change the conditions for the specified file, and
execute the request again.
• Reduce the file operation, and execute the request
again.
• Check the size of the specified file, and execute the
request again.
• Check the size of the specified file, and execute the
request again.
• Change the target drive (memory), and execute the
request again.
• Change the specified drive (memory), and execute the
request again.
• Perform the operation from the control CPU module for
the target module.
• Check the buffer memory address, and execute the
request again.
• Do not initialize the target drive (memory) since it
cannot be initialized.
• Do not delete the target file/folder since it cannot be
deleted.
• Check the file, and execute the request again.
• The function to write data to the program memory, or
the function to transfer data to backup memory is being
performed.
Check the completion of the above functions, and
execute the request again.
• Execute the request again once the currently
performed operation has been completed.
• Write all the required files to the programmable
controller.
• Perform the remote Y OUT or remote RUN operation
again after a while.
• Execute it again after a while.
If the same error code is displayed again, the possible
cause is a hardware failure of the target module. Please
contact your local Mitsubishi Electric sales office or
representative.
• Check the target module of the error clear function.
(Check the module on which an error occurred.)
• Correct the network number and station number of a
user program.
• Set the routine parameters to the related stations for
accessing the specified station.
• Retry it after a while. Or, check the startup of the
system that relays data, and start communication.
• Set the CPU module that relays IP packets to the
control CPU module for the CC-Link IE module on the
path where IP packet travel.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-r melsecwincpu

Table of Contents