Error
Error name
code
1863H
Memory error
1864H
Service error
1865H
Service error
1866H
Communication error
1867H
Service error
1868H
Service error
1869H
Service error
2000H
Module configuration
error
2001H
Module configuration
error
2002H
Module configuration
error
2004H
Module configuration
error
Error details and cause
• Reserving sufficient memory failed.
• Starting a Windows service failed.
• A Windows service ended with an
error.
• A socket error occurred.
• An error occurred in a Windows
service.
• Starting a Windows service failed.
• An error occurred in a Windows
service.
• The module type set in the system
parameters (I/O assignment setting)
differs from that of the module
actually mounted.
• The I/O numbers set in the system
parameters (I/O assignment setting)
are overlapping between modules.
• The number of points assigned to the
intelligent function module in the
system parameters (I/O assignment
setting) is smaller than that of the
module actually mounted.
• Nine or more CC-Link IE Controller
Network* and MELSECNET/H
modules are mounted in the entire
system.
* The CC-Link IE built-in Ethernet
interface module is included if the
module is used as a CC-Link IE
Controller Network module.
• Five or more MELSECNET/H
modules are mounted in the entire
system.
Corrective action
• Restart Windows. If the same error
code is displayed again, the possible
cause is a hardware failure of the
CPU module. Please contact your
local Mitsubishi Electric sales office or
representative.
• Restart Windows. If the same error
code is displayed again, the possible
cause is a hardware failure of the
CPU module. Please contact your
local Mitsubishi Electric sales office or
representative.
• Restart Windows. If the same error
code is displayed again, the possible
cause is a hardware failure of the
CPU module. Please contact your
local Mitsubishi Electric sales office or
representative.
• Restart Windows. If the same error
code is displayed again, the possible
cause is a hardware failure of the
CPU module. Please contact your
local Mitsubishi Electric sales office or
representative.
• Restart Windows. If the same error
code is displayed again, the possible
cause is a hardware failure of the
CPU module. Please contact your
local Mitsubishi Electric sales office or
representative.
• Restart Windows. If the same error
code is displayed again, the possible
cause is a hardware failure of the
CPU module. Please contact your
local Mitsubishi Electric sales office or
representative.
• Restart Windows. If the same error
code is displayed again, the possible
cause is a hardware failure of the
CPU module. Please contact your
local Mitsubishi Electric sales office or
representative.
• Re-set the module type in the system
parameters in accordance with the
CPU module or intelligent function
module actually mounted.
• Re-set the I/O numbers in the system
parameters in accordance with the
intelligent function module or I/O
module actually mounted.
• Re-set the number of points in the
system parameters in accordance
with the intelligent function module
actually mounted.
• Reduce the number of CC-Link IE
Controller Network* and
MELSECNET/H modules to eight or
less in the entire system.
* The CC-Link IE built-in Ethernet
interface module is included if the
module is used as a CC-Link IE
Controller Network module.
• Reduce the number of MELSECNET/
H modules to four or less in the entire
system.
33.1 Error Codes for Self-diagnostics
Stop/
Diagnostic
continue
timing
Continue
Always
Continue
Always
Continue
Always
Continue
Always
Continue
Always
Continue
Always
Continue
Always
Stop
Power-on,
hardware
reset, bus
reset
Stop
Power-on,
hardware
reset, bus
reset
Stop
Power-on,
hardware
reset, bus
reset
Stop
Power-on,
hardware
reset, bus
reset