24
Y OUTPUT CONTROL FUNCTION
This function controls the Y output status (Y STOP/Y OUT/PAUSE) with the BUS RESET/Y STOP/Y OUT switch or a
MELSEC data link function.
For details on the Y output status of this product, refer to the following:
Page 28 Y output status
Changing the Y output status
The following table shows the methods for changing the Y output status.
Method
Switch operation
MELSEC data link function
Remote operation from another
station
*1 Specify STOP (Y STOP) or RUN (Y OUT) when performing the remote operation from a tool other than CW Configurator.
• The switch operation takes priority to set the Y output status. When the BUS RESET/Y STOP/Y OUT switch
is set to Y STOP, the Y output status cannot be changed to Y OUT state with a MELSEC data link function
and remote operation.
• If the Y output status is changed to the Y STOP state by remote operation, it can be changed to Y OUT state
only from a tool or another station that performs the remote operation.
■Y output status when an error occurs
Refer to the following:
Page 208 Operation Setting When an Error is Detected
■Y output status when a switch is operated or a stop error occurs
: No status change
Y output status before change
Factor to determine
Y output status
the Y output status
BUS RESET/Y STOP/Y
Y STOP
OUT switch
Y OUT
Remote operation from CW
Y STOP
Configurator or a module
PAUSE
(The actual operating status
is Y STOP.)
Y OUT
(The actual operating status
is Y STOP.)
Y STOP
PAUSE
Y OUT
Operation
Change the BUS RESET/Y STOP/Y OUT switch from Y OUT to Y
STOP.
Change the BUS RESET/Y STOP/Y OUT switch from Y STOP to Y
OUT.
Specify STOP with the mdControl function.
Specify RUN with the mdControl function.
Specify PAUSE with the mdControl function.
Specify Y STOP with a remote operation.
Specify Y OUT with a remote operation.
Specify PAUSE with a remote operation.
Switch status
Y STOP
Y OUT
Y STOP
Y STOP
Y STOP
Y OUT
Y OUT
Y OUT
Y STOP LED
status
ON in orange
OFF
ON in orange
OFF
Flashing in orange
*1
ON in orange
*1
OFF
Flashing in orange
Y output status after change
BUS RESET/Y STOP/Y OUT switch
Y OUT
Y STOP
Y OUT
Y STOP
PAUSE
Y OUT
Y STOP
Y STOP
24 Y OUTPUT CONTROL FUNCTION
Y output status
Y STOP state
Y OUT state
Y STOP state
Y OUT state
PAUSE state
Y STOP state
Y OUT state
PAUSE state
24
Stop error
occurred
Y STOP
Y STOP
Y STOP
197