Error
Error name
code
4033H
Device specification
error
4040H
Intelligent function
module specification
error
4041H
Intelligent function
module specification
error
4042H
Intelligent function
module specification
error
4043H
Intelligent function
module specification
error
4044H
Intelligent function
module specification
error
4052H
Protect error
4053H
Protect error
4054H
Protect error
4080H
Other error
4082H
Other error
408BH
Other error
4121H
File related error
4122H
File related error
4123H
File related error
4124H
File related error
4125H
File related error
4129H
File related error
412AH
File related error
412BH
File related error
412DH
File related error
412EH
File related error
412FH
File related error
4130H
File related error
4131H
File related error
4132H
File related error
Error details and cause
• Data cannot be written to the specified device since it
is for system use.
• The request cannot be executed to the specified
intelligent function module.
• The access range exceeded the buffer memory range
of the specified intelligent function module.
• The specified intelligent function module cannot be
accessed.
• The specified intelligent function module does not
exist.
• A bus error occurred during the access to an intelligent
function module.
• Data cannot be written since the specified file attribute
is the read-only.
• An error occurred when writing data to the specified
drive (memory).
• An error occurred when deleting data from the
specified drive (memory).
• Request data error
• The specified command cannot be executed since it is
being executed.
• A remote request cannot be executed.
• The specified drive (memory) or file does not exist.
• The specified drive (memory) or file does not exist.
• The specified drive (memory) has an error.
• The specified drive (memory) has an error.
• The specified drive (memory) or file is currently being
processed.
• The request cannot be executed since the specified
drive (memory) is ROM.
• The request cannot be executed since the specified
drive (memory) is ROM.
• The specified drive (memory) is write-prohibited.
• The specified drive (memory) does not have enough
free space.
• The specified drive (memory) does not have enough
free space.
• The drive (memory) capacity differs between the copy
destination and the copy source.
• The drive (memory) type differs between the copy
destination and the copy source.
• The file name of the copy destination is the same as
the one of the copy source.
• The specified number of files does not exist.
Corrective action
• Do not write data to the specified device. Or, do not
turn it ON/OFF.
• Check whether the specified module is an intelligent
function module which has the buffer memory.
• Check the start address and number of access points,
and access within the range that exists in the intelligent
function module.
• Check whether the specified intelligent function
module operates normally.
• Check whether the specified module has hardware
failure.
• Check the I/O number of the specified intelligent
function module.
• Check whether the specified intelligent function
module, other modules, or base unit have hardware
failure.
• Do not write data to the specified file. Or, change the
file attribute.
• Check the specified drive (memory). Or, write data
again after changing the target drive (memory).
• Check the specified drive (memory). Or, delete data
again after changing the target drive (memory).
• Check the specified request data.
• Execute the command again once the request from
another engineering tool has been completed.
• Execute the request again after placing the CPU
module in the state where a remote request can be
executed.
• For the remote BUS RESET operation, set "Enable" for
"Remote Bus Reset Setting" with the parameter.
• Check the specified drive (memory) or file, and
execute the request again.
• Check the specified drive (memory) or file, and
execute the request again.
• Initialize the memory, and restore the drive (memory)
to its normal state.
• Initialize the memory, and restore the drive (memory)
to its normal state.
• Execute it again after a while.
• Change the target drive (memory), and execute the
request again.
• Change the target drive (memory), and execute the
request again.
• Change the write-protect conditions or drive (memory),
and execute the request again.
• Increase the free space of the drive (memory), and
execute the request again.
• Increase the free space of the drive (memory), and
execute the request again.
• Check the copy destination and copy source drive
(memory), and execute the request again.
• Check the copy destination and copy source drive
(memory), and execute the request again.
• Check the file name, and execute the request again.
• Check the specified data, and execute the request
again.