Appendix 2 Windows Event List - Mitsubishi Electric MELSEC iQ-R Series User Manual

Programmable controller
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Appendix 2
This sections shows the list of events that occur on Windows in this product.
Event ID
Event type
0010
System
0011
System
0032
System
0064
System
0096
System
0097
System
0512
System
0513
System
0576
System
0704
System
0768
System
0769
System
0770
System
0771
System
2048
System
2049
System
2050
System
2080
System
2560
System
2561
System
2562
System
APPX
268

Appendix 2 Windows Event List

Windows Event List
Event
Description
category
Information
A service was started.
Information
A service was ended.
Information
A service was ended.
Information
An event of the MELSEC function was registered.
Information
Parameters have been updated.
Information
Windows was started or the bus was reset.
Information
The number of connected MELSOFT connection
modules exceeded the maximum number.
Information
The TCP connection time-out was detected.
Information
The Windows time has changed.
Information
A notification of parameter update was received.
Information
Current consumption of a USB port exceeded the
threshold.
Information
A USB port has stopped working because its
current consumption exceeded the threshold.
Information
All the USB ports have stopped working because
their current consumption exceeded the threshold.
Information
A current consumption error was cleared.
Warning
Sending data failed.
Warning
Receiving data timed out.
Warning
Receiving data failed.
Warning
A minor error of the MELSEC function was
registered.
Warning
An invalid frame (packet) was received from a
MELSOFT connection module.
Warning
A unicast frame (packet) was received on the
broadcast UDP port.
Warning
Receiving a frame (packet) from a MELSOFT
connection module failed.
Corrective action
For details, refer to the manual displayed as a link.
Reset the bus and restart Windows.
If the same event is registered again, the possible
cause is a hardware failure. Please contact your
local Mitsubishi Electric sales office or
representative.
Try again after a while.
If the same event is registered again, reset the bus
and restart Windows.
If the problem is still not resolved, the possible
cause is a hardware failure. Please contact your
local Mitsubishi Electric sales office or
representative.
Reset the bus and restart Windows.
If the same event is registered again, the possible
cause is a hardware failure. Please contact your
local Mitsubishi Electric sales office or
representative.
For details, refer to the manual displayed as a link.
Check if the connected modules and Windows
applications use any of the following system port
numbers:
• 5006 to 5100
If so, take the following corrective actions and try
again.
• Review the port number of the module.
• End the application.
Check if the connected modules and Windows
applications use any of the following system port
numbers:
• 5006 to 5100
If so, take the following corrective actions and try
again.
• Review the port number of the module.
• End the application.
• A line may be congested with packets. Try again
after a while.
• Check if there is any error in the connection of
the cable and switching hub.
• Check if the cable is disconnected.