Error code (HEX)
0x80010005
0x80010007
0x8001000A
0x8001000C
0x80010011
0x80010012
0x80010013
218
4. TROUBLE INDICATION
4.1 Error code
Error message
Because of incorrect wiring, data
was transmitted before
completing a data reception.
The inverter received an
unusable character (other than 0
to 9, A to F, or control codes).
A mode error occurred.
Any value outside the setting
range cannot be written.
The parameter outside the
setting range cannot be written.
A mode error occurred.
No parameter can be written
during inverter running.
Possible cause
• The settings of Pr.123 PU
communication waiting time
setting and Pr.337 RS-485
communication waiting time
setting are too small.
• Electromagnetic interference.
• Cable breakage.
• The Pr.119 PU communication
stop bit length / data length and
Pr.333 RS-485 communication
stop bit length / data length
settings are different with the
software settings.
• Electromagnetic interference.
• Cable breakage.
A test operation was attempted
without setting FR Configurator2 as
the operation (start) command
source, for example in the External
operation mode (EXT).
An out-of-range value or operation
frequency was written to the
parameter.
An out-of-range value was written
to the parameter.
• Pr.79 Operation mode
selection is not set for PU/NET
(RS-485).
• A parameter or frequency setting
was attempted without setting FR
Configurator2 as such command
source, for example in the
External operation mode (EXT).
Parameter writing was attempted
during inverter operation.
Countermeasure
• Set a larger value or "9999" in
Pr.123 PU communication waiting
time setting and Pr.337 RS-485
communication waiting time
setting.
• Set a larger value in Pr.121 PU
communication retry count and
Pr.335 RS-485 communication
retry count.
• Replace the cable.
• Match the Pr.119 PU
communication stop bit length /
data length and Pr.333 RS-485
communication stop bit length /
data length settings with the
software settings.
• Set a larger value in Pr.121 PU
communication retry count and
Pr.335 RS-485 communication
retry count.
• Replace the cable.
• Change the operation mode to the
PU operation mode (or NET).
• Check the setting values of Pr.338
Communication operation
command source, Pr.550 NET
mode operation command source
selection, and Pr.551 PU mode
operation command source
selection. (The operation command
source changes according to
inverter communication connection.
Refer to
26
and
page
65.)
Set a value within the setting range,
and enter the setting.
If a writing error occurs even if a value
within the setting range is written,
check for the writing requirements for
each parameter. For the details on the
writing requirements, refer to the
Instruction Manual of the inverter.
Set a value within the setting range,
and enter the setting.
If a writing error occurs even if a value
within the setting range is written,
check for the writing requirements for
each parameter. For the details on the
writing requirements, refer to the
Instruction Manual of the inverter.
• Click [PU] button of Test Operation.
Change the setting of Pr.79 for PU/NET
(RS-485).
• Change the operation mode to the
PU operation mode (or NET).
• Check the setting values of Pr.339
Communication speed command
source, Pr.550 NET mode
operation command source
selection, and Pr.551 PU mode
operation command source
selection. (The speed command
source changes according to
inverter communication connection.
Refer to
26
and
page
65.)
Perform parameter writing after the
inverter is stopped.