• When parameter settings are converted from FR-A700 (FM type) inverters to FR-A800 (CA type) inverters or from FR-
A700 (CA type) inverters to FR-A800 (FM type) inverters, set the following parameters as required in the "Parameter list"
window because they are not converted.
Pr.54 FM/CA terminal function selection
Pr.291 Pulse train I/O selection
Pr.869 Current output filter
C8 (Pr.930) to C11 (Pr.931) (Terminal CA calibration parameters)
• It is recommended to adjust the setting of the following parameters again after conversion according to the mechanical
system because they are used for adjustment.
Pr.0 Torque boost
Pr.12 DC injection brake operation voltage
C2 (Pr.902) to C7 (Pr.905) (Frequency setting input calibration parameters)
• Since the communication-related parameters (Pr.117 to Pr.124, Pr.331 to Pr.337, Pr.341, Pr.547, and Pr.548) are also
converted, communication may be disabled depending on the setting after the setting is written to parameters. For
example, when Pr.122/Pr.336 RS-485 communication check time interval = "0 (initial value)", a communication error
(E.PUE, E.SER) occurs immediately after the operation mode with the command source is selected.
• The parameters for the FR-A7AL function (Pr.413, Pr.432, and Pr.433) are not converted because the FR-A800 series
inverters have no corresponding parameters.
• If "63" is set in Pr.184 AU terminal function selection to enable the PTC thermal error detection (E.PTC) in the source
FR-A700 inverter, setting of Pr.561 and Pr.1016 and connecting the motor to the target FR-A800 inverter via terminals 2
and 10 are required. For the parameter details and terminal connection, refer to the Instruction Manual of the inverter.
 To convert from FR-A700 inverters to FR-A802(-E) inverters
When the parameter settings are converted to the separated converter type, check the following items in addition to the items
mentioned in the previous page.
• After converting parameters, assign the X10 signal to an input terminal by setting of any of Pr.178 to Pr.189, and connect
the signal to the RDA signal of the FR-CC2.
• After converting parameters, assign the RES signal to an input terminal by setting of any of Pr.178 to Pr.189, and connect
the signal to the RSO signal of the FR-CC2.
• Set the following parameter as required in the "Parameter list" window because they are not converted depending on the
setting of the source inverter.
Pr.30 Regenerative function selection
Pr.52 Operation panel main monitor selection
Pr.54 FM/CA terminal function selection
Pr.158 AM terminal function selection
Pr.178 to Pr.189, Pr.190 to Pr.196 (I/O terminal function assignment)
Pr.306 Analog output signal selection
Pr.310 Analog meter voltage output selection
Pr.313 to Pr.322 (Output selection)
Pr.599 X10 terminal input selection
*1
Available when the plug-in option is connected.
126
3. FUNCTION
3.3 Convert