 Precautions for writing Ethernet parameters
To apply written setting values, perform inverter reset. When inverter reset is attempted, the following window appears. When
multiple inverters are connected in line topology, click on the checkbox. Otherwise, the inverter is not reset properly.
• When inverters are connected in line topology, perform inverter reset for each inverter one by one. The time required to
complete the operation differs depending on the number of connected inverters. Total time = Number of inverters × 5 s
• When it takes a long time, it is alternatively possible to reset the inverters by turning OFF and ON the power of each
inverter.
 Ethernet parameter settings in the inverter and FR Configurator2
• Before using the Ethernet parameter setting, check the setting of parameters in the following table.
Model
Intermediate
device
FR-A800-E
Not connected
FR-F800-E
FR-A800-E-
Not connected
R2R
FR-E800-
Not connected
(SC)E
FR-E700-NE
Not connected

3.12.2 Batch assignment dialog

Batch assignment can be performed to assign the network number, station number, IP address, and subnet mask
automatically.
184
3. FUNCTION
3.12 Ethernet parameter setting function
Pr.
Name
1427
Ethernet function selection 1
1428
Ethernet function selection 2
1429
Ethernet function selection 3
IP filter address (Ethernet)
1442 to 1448
1076
Ethernet function selection 1
1077
Ethernet function selection 2
1078
Ethernet function selection 3
IP filter address (Ethernet)
1442 to 1448
1427
Ethernet function selection 1
1428
Ethernet function selection 2
1429
Ethernet function selection 3
1430
Ethernet function selection 4
IP filter address (Ethernet)
1442 to 1448
833
Ethernet function selection 1
834
Ethernet function selection 2
835
Ethernet function selection 3
Ethernet IP filter address
837 to 843
Setting
Set a combination of "5001" (or "5002") and
"45237" in any two of the parameters.
Set the IP address to within the IP address range
of the personal computer.
Set a combination of "5001" (or "5002") and
"45237" in any two of the parameters.
Set the IP address to within the IP address range
of the personal computer.
Set a combination of "5001" (or "5002") and
"45237" in any two of the parameters.
Set the IP address to within the IP address range
of the personal computer.
Set a combination of "31" and "20" in any two of the
parameters.
Set the IP address to within the IP address range
of the personal computer.