3.19 LC-## Logic Controller

Parameter group related to programming the drive's built-
in Logic Controller. The Logic Controller consists of a series
of user defined actions (see LC-52 Logic Controller Action)
that are executed when the corresponding user-defined
events are met.
3.19.1 LC-0# LC Settings
Parameters to configure the activation, deactivations and
reset of the Logic Controller (LC).
LC-00 Logic Controller Mode
Option:
Function:
[0]
Off
Disables the Logic Controller.
*
[1]
On
Enables the Logic Controller.
LC-01 Start Event
Select the boolean (TRUE or FALSE) input to activate Logic
Controller.
Option:
Function:
[0]
False
Select the boolean (TRUE or FALSE)
*
input to activate Logic Controller.
Enters the fixed value - FALSE
[1]
True
Enters the fixed value - TRUE.
[2]
Running
The motor is running.
[3]
In range
The motor is running within the
programmed current and speed
ranges set in H-70 Warning Current
Low to H-73 Warning Speed High.
[4]
On reference
The motor is running on reference.
[5]
Torque limit
The torque limit, set in F-40 Torque
Limiter (Driving) or F-41 Torque Limiter
(Braking), has been exceeded.
[6]
Current Limit
The motor current limit, set in
F-43 Current Limit, has been
exceeded.
[7]
Out of current
The motor current is outside the
range
range set in F-43 Current Limit.
[8]
Below I low
The motor current is lower than set
in H-70 Warning Current Low.
[9]
Above I high
The motor current is higher than set
in H-71 Warning Current High.
[10]
Out of speed range The speed is outside the range set in
H-72 Warning Speed Low and
H-73 Warning Speed High.
[11]
Below speed low
The output speed is lower than the
setting in H-72 Warning Speed Low.
[12]
Above speed high
The output speed is higher than the
setting in H-73 Warning Speed High.
AF-650 GP Programming Guide
LC-01 Start Event
Select the boolean (TRUE or FALSE) input to activate Logic
Controller.
Option:
[13]
Out of feedb. range The feedback is outside the range set
[14]
Below feedb. low
[15]
Above feedb. high
[16]
Thermal warning
[17]
Line voltage out of
range
[18]
Reversing
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip lock)
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
[27]
Logic rule 1
[28]
Logic rule 2
[29]
Logic rule 3
[33]
Digital input DI18
[34]
Digital input DI19
[35]
Digital input DI27
[36]
Digital input DI29
[37]
Digital input DI32
[38]
Digital input DI33
[39]
Start command
[40]
Drive stopped
[41]
Reset Trip
[42]
Auto-reset Trip
[43]
Ok key
DET-618C
Function:
in H-76 Warning Feedback Low and
H-77 Warning Feedback High.
The feedback is below the limit set in
H-76 Warning Feedback Low.
The feedback is above the limit set in
H-77 Warning Feedback High.
The thermal warning turns on when
the temperature exceeds the limit in
the motor, the frequency converter,
the brake resistor or the thermistor.
The mains voltage is outside the
specified voltage range.
The output is high when the
frequency converter is running
counter clockwise (the logical product
of the status bits "running" AND
"reverse").
A warning is active.
A (trip) alarm is active.
A (Trip lock) alarm is active.
Use the result of comparator 0.
Use the result of comparator 1.
Use the result of comparator 2.
Use the result of comparator 3.
Use the result of logic rule 0.
Use the result of logic rule 1.
Use the result of logic rule 2.
Use the result of logic rule 3.
Use the result of digital input 18.
Use the result of digital input 19.
Use the result of digital input 27.
Use the result of digital input 29.
Use the result of digital input 32.
Use the result of digital input 33.
A start command is issued.
A stop command (Jog, Stop, Qstop,
Coast) is issued – and not from the
Logic Controller itself.
A reset is issued
An Auto reset is performed.
[OK] is pressed.