4.10. Parameter Group 13: Logic Controller

4.10.1. 13-** Programming Features
Logic Controlleris a sequence of user defined actions (par. 13-52 [X]) executed by the Logic Controller when the associated user defined event (par. 13-51 [X]) is
set to True.
Events and actions are linked in pairs, meaning that when an event is true, the linked action is carried out. After this the next event is evaluated and its belonging
action carried out and so on. Only one event is evaluated at the time.
If an event is evaluated as False, the Logic Controller takes no action during the scan interval and no other events are evaluated.
It is possible to programme from 1 to 20 events and actions.
When the last event/action has been executed, the sequence starts again from event/action [0].
The drawing shows an example with three events/actions:
Starting and stopping the Logic Controller:
Start the Logic Controller by selecting On [1] in par. 13-00. The Logic Controller starts evaluating Event 0, and if this is evaluated as TRUE, the Logic Controller
continues its cycle.
The Logic Controller stops when the Stop Event, par. 13-02, is TRUE. The Logic Controller can also be stopped by selecting Off [0] in par. 13-00.
To reset all Logic Controller parameters select Reset Logic Controller [1] in par. 13-03 and start programming from scratch.
4.10.2. 13-0* Logic Controller Settings
Use Logic Controller settings to activate, deactive and reset the Logic Controller.
13-00 Logic Controller Mode
Option:
*
Off
[0]
Function:
Function is disabled.