Section 15 Protection Relay And Functionality Tests - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
Section 15
REX640
Technical Manual
Protection relay and functionality tests
Table 1507:
Electromagnetic compatibility tests
Description
1 MHz/100 kHz burst
disturbance test
Common mode
Differential mode
3 MHz, 10 MHz and 30 MHz
burst disturbance test
Common mode
Electrostatic discharge test
Contact discharge
Air discharge
Radio frequency interference
test
Fast transient disturbance test
Communication
Other ports
Surge immunity test
Communication
Other ports
Power frequency (50 Hz)
magnetic field immunity test
Table continues on next page
Protection relay and functionality tests
Type test value
2.5 kV
2.5 kV
2.5 kV
8 kV
15 kV
10 V (rms)
f = 150 kHz...80 MHz
10 V/m (rms)
f = 80...2700 MHz
10 V/m
f = 900 MHz
20 V/m (rms)
f = 80...1000 MHz
2 kV
4 kV
1 kV, line-to-earth
4 kV, line-to-earth
2 kV, line-to-line
Section 15
Reference
IEC 61000-4-18
IEC 60255-26, class III
IEEE C37.90.1-2012
IEC 61000-4-18
IEC 60255-26, class III
IEC 61000-4-2
IEC 60255-26
IEEE C37.90.3-2001
IEC 61000-4-6
IEC 60255-26, class III
IEC 61000-4-3
IEC 60255-26, class III
ENV 50204
IEC 60255-26, class III
IEEE C37.90.2-2004
IEC 61000-4-4
IEC 60255-26
IEEE C37.90.1-2012
IEC 61000-4-5
IEC 60255-26
IEC 61000-4-8
IEC 60255-26
1741

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents