6.2.7 Querying Slave SmartLogger Information

This topic describes how to query Slave SmartLogger information on the monitoring panel.
Context
The Slave SmartLogger mainly applies to power grid scheduling of large-sized power stations.
One SmartLogger can connect to a maximum of 80 devices. When there are more than 80
inverters in the power station, a certain number of Slave SmartLoggers should be configured.
The power grid scheduling command sent to the Master SmartLogger is synchronized to the
Slave SmartLogger to enable the centralized power grid scheduling of the power station.
Devices can only be manually added and removed in the Slave SmartLogger on the
monitoring panel or the embedded WebUI.
The Slave SmartLogger and the Master SmartLogger should be within the same local area
network (LAN).
Procedure
LCD
Issue 12 (2019-01-15)
To query Slave SmartLogger information, perform the steps described in the following
table. The parameter values in the figures are for reference only.
Copyright © Huawei Technologies Co., Ltd.
Procedure
1. On the default screen, press
the main menu.
2. Select
and press
6 User Interface
to enter
.
76