SmartLogger1000
User Manual
No.
Parameter
35
Level-5 UV
protection
time
Level-6 UV
36
protection
37
Level-6 UV
protection
time
Level-3 OF
38
protection
39
Level-3 OF
protection
time
40
Level-4 OF
protection
41
Level-4 OF
protection
time
42
Level-5 OF
protection
43
Level-5 OF
protection
time
44
Level-6 OF
protection
Level-6 OF
45
protection
time
46
Level-3 UF
protection
Level-3 UF
47
protection
time
48
Level-4 UF
protection
Issue 12 (2019-01-15)
Description
Specifies the level-5
undervoltage protection
duration.
Specifies the level-6
undervoltage protection
threshold.
Specifies the level-6
undervoltage protection
duration.
Specifies the level-3
overfrequency protection
threshold.
Specifies the level-3
overfrequency protection
duration.
Specifies the level-4
overfrequency protection
threshold.
Specifies the level-4
overfrequency protection
duration.
Specifies the level-5
overfrequency protection
threshold.
Specifies the level-5
overfrequency protection
duration.
Specifies the level-6
overfrequency protection
threshold.
Specifies the level-6
overfrequency protection
duration.
Specifies the level-3
underfrequency
protection threshold.
Specifies the level-3
underfrequency
protection duration.
Specifies the level-4
underfrequency
protection threshold.
Copyright © Huawei Technologies Co., Ltd.
Unit
Value Range
ms
[50, 7200000]
V
[0.15 x Vn, 1 x Vn]
ms
[50, 7200000]
Hz
[1 x Fn, 1.15 x Fn]
ms
[50, 7200000]
Hz
[1 x Fn, 1.15 x Fn]
ms
[50, 7200000]
Hz
[1 x Fn, 1.15 x Fn]
ms
[50, 7200000]
Hz
[1 x Fn, 1.15 x Fn]
ms
[50, 7200000]
Hz
[0.85 x Fn, 1 x Fn]
ms
[50, 7200000]
Hz
[0.85 x Fn, 1 x Fn]
7 WebUI
Remarks
Vn represents the
rated voltage.
Fn represents the
rated frequency.
Fn represents the
rated frequency.
Fn represents the
rated frequency.
Fn represents the
rated frequency.
Fn represents the
rated frequency.
Fn represents the
rated frequency.