Huawei SmartLogger1000 User Manual page 200

Hide thumbs Also See for SmartLogger1000:
Table of Contents

Advertisement

SmartLogger1000
User Manual
No.
Parameter
49
Level-4 UF
protection
time
Level-5 UF
50
protection
51
Level-5 UF
protection
time
Level-6 UF
52
protection
53
Level-6 UF
protection
time
54
Overfreque
ncy
protection
threshold
55
Overfreque
ncy
protection
duration
56
Underfrequ
ency
protection
threshold
Underfrequ
57
ency
protection
duration
58
AC
overvoltage
protection
threshold
59
AC
overvoltage
protection
duration
Issue 12 (2019-01-15)
Description
Specifies the level-4
underfrequency
protection duration.
Specifies the level-5
underfrequency
protection threshold.
Specifies the level-5
underfrequency
protection duration.
Specifies the level-6
underfrequency
protection threshold.
Specifies the level-6
underfrequency
protection duration.
Specifies the grid
overfrequency protection
threshold.
Specifies the grid
overfrequency protection
duration.
Specifies the grid
underfrequency
protection threshold.
Specifies the grid
underfrequency
protection duration.
Specifies the grid
overvoltage protection
threshold.
Specifies the grid
overvoltage protection
duration.
Copyright © Huawei Technologies Co., Ltd.
Unit
Value Range
ms
[50, 7200000]
Hz
[0.85 x Fn, 1 x Fn]
ms
[50, 7200000]
Hz
[0.85 x Fn, 1 x Fn]
ms
[50, 7200000]
Hz
50 Hz: 50.5 Hz,
51.0 Hz, 51.5 Hz, and
52.0 Hz
60 Hz: 60.6 Hz, 61.2
Hz, 61.8 Hz, and 62.4
Hz
s
0.5s, 1.0s, 1.5s, and 2.0s
Hz
50 Hz: 49.5 Hz,
49.0 Hz, 48.5 Hz,
48.0 Hz, 47.5 Hz, and
47.0 Hz
60 Hz: 59.6 Hz, 59.0
Hz, 58.4 Hz, 57.8 Hz,
and 57.2 Hz
s
0.5s, 1.0s, 1.5s, and 2.0s
V
110.0 V, 112.5 V, 115.0
V, and 120.0 V
s
0.5s, 1.0s, 1.5s, and 2.0s
7 WebUI
Remarks
Fn represents the
rated frequency.
Fn represents the
rated frequency.
N/A
N/A
N/A
N/A
N/A
N/A
187