Figure 4-24 Stripping a cable (unit: mm)
Step 3 Insert the bare core wires into the surge port of the RS485 signal SPD, as shown by (1) in
Figure
Figure 4-25 Connecting cables to the surge port of the RS485 signal SPD
Verify that the RS485+ port on the analog-to-digital converter connects to surge port 1 or 7 on
the RS485 signal SPD, and that the RS485– port on the analog-to-digital converter connects
to surge port 5 or 11 on the RS485 signal SPD.
Step 4 Use a flat-head screwdriver to tighten the screws on the surge ports, as shown by (2) in
4-25.
Step 5 Set Baud rate for the analog-to-digital converter to the same value as that for the
SmartLogger.
Step 6 Connect each sensor to the analog-to-digital converter. For detailed operations, see the
documents delivered with the analog-to-digital converter or sensors.
Issue 12 (2019-01-15)
4-25.
SmartLogger communications parameters can be set on the LCD or WebUI. For details,
see
6.2.26 Setting Communications Parameters
For details about the communications parameter configurations for the analog-to-digital
converter, see the delivered document.
After connecting the cables, log in to the embedded WebUI and set relevant parameters. For details,
see
7.8.4.2 Setting EMI
The EMI cannot be detected automatically. You need to add this device manually on the LCD or
WebUI. For details about this operation, see
Devices.