Parameter
Start Current (mA)
End Current (mA)
Start Data
End Data

7.10.2.4 Setting Management System Parameters

To set parameters correctly, ensure that the SmartLogger can connect to Huawei management
systems, such as NetEco and FusionSolar, or a third-party management system.
Because of permission restriction, log in as Advanced User. Choose Settings >
Management System to access the page.
Figure 7-48 Setting management system parameters
Issue 12 (2019-01-15)
Set Server to the IP address or domain name of the management system server.
If the SmartLogger connects to the Huawei management system, retain the default value 16100 for
Port number. If it connects to a third-party management system, set Port number based on the
server port enabled in the third-party management system.
Generally, Address mode is set to Comm. Address. If the devices connected to the three RS485
ports on the SmartLogger have duplicate addresses, Address mode must be set to Logical address.
If SSL encryption is set to Disable, data will be transmitted without being encrypted, which may
result in user data theft. Therefore, exercise caution when deciding to set SSL encryption to
Disable.
If Second challenge authentication is set to Disable, the second challenge authentication result will
not be verified, which may result in user data theft. Therefore, exercise caution when deciding to set
Second challenge authentication to Disable.
Obtain the documents about security certificate from the management system.
Copyright © Huawei Technologies Co., Ltd.
Description
Indicates the valid value range of signals carried by the
analog output loop. The current range is less than or equal to
the current range set in the AO specifications. Start Data
corresponds to End Data.
Indicates the valid value range of signals of Feedback
Parameter. Set the two parameters as required. An excessive
range results in low precision of the feedback while an
insufficient range results in the incompleteness of the
feedback.