Huawei SmartLogger1000 User Manual page 206

Hide thumbs Also See for SmartLogger1000:
Table of Contents

Advertisement

SmartLogger1000
User Manual
Power Adjustment Parameters
Table 7-9 Parameter description
No.
Parameter
1
Active power
change
gradient
2
Fixed active
power derated
Active power
3
percentage
derating
4
Reactive
power change
gradient
5
Power factor
7
Overfrequenc
y derating
8
Trigger
frequency of
over
frequency
derating
Issue 12 (2019-01-15)
Description
Adjusts the change speed
of the inverter active
power.
Adjusts the active power
output of the inverter in
fixed values.
Adjusts the active power
output of the inverter in
percentages.
Adjusts the change speed
of the inverter reactive
power.
Adjusts the power factor
of the inverter.
If this parameter is
enabled, the active power
of the inverter will be
derated according to a
certain slope when the
grid frequency exceeds
the value that triggers
overfrequency derating.
The standards of certain
countries and regions
require that the output
active power of the
inverter should be derated
when the power grid
frequency exceeds a
certain value.
Copyright © Huawei Technologies Co., Ltd.
Unit
Value Range
%/s
1000 V inverter:
[0.1, 50]
Others: [0.1,
1000]
600
1000 V inverter:
V
[0, Pmax]
inve
Others: [0,
rter:
Pmax_limit]
W
Oth
ers:
kW
%
[0, 100]
%/s
[0.1, 1000]
N/A
(–1.000,
–0.800]U[0.800,
1.000]
N/A
Disable
Enable
Hz
When the output
frequency is 50 Hz,
the value range is
[45.00, 55.00].
When the output
frequency is 60 Hz,
the value range is
[55.00, 65.00].
7 WebUI
Remarks
N/A
Pmax represents the
maximum active
power.
In the 1000 V
inverter, the upper
threshold for the
SUN2000-25KTL-U
S is 27.5 kW, and the
upper threshold for
other models of
inverters is Pmax.
If this parameter is
set to 100, the
inverter delivers the
maximum output
power.
N/A
N/A
N/A
This parameter is
for the inverters
except the 1000 V
ones. It is
displayed when
Overfrequency
derating is set to
Enable.
193