Operation Procedure
6. Set RS485 parameters and then press
The following baud rates are
supported:2400 bps, 4800 bps, 9600 bps,
19200 bps and 115200 bps. 9600 bps is
recommended.
1 ≤ Start Address ≤ End Address ≤ 247.
The address segments for these three ports
can overlap.
Set the address scope properly. The
broader the scope is, the longer the time is
for searching the devices.
Stop Bit supported by the SmartLogger is
1 or 2.
Protocol, Parity, and Stop Bit must be set
to the same values for all devices
connected to the same RS485 port.
7. Press
, select Ethernet, and press
8. Set Ethernet parameters and then press
NOTE
If the SmartLogger connects to the Internet through
a router, note the following when setting Ethernet
parameters:
If you set Auto obtain IP to Enable, the DHCP
server on the network assigns IP addresses. In
this case, you must ensure that a DHCP server is
working on the network.
Set the gateway address to the IP address of the
router.
Ensure that the IP address of the SmartLogger is
in the same network segment as the gateway
address.
Set the domain name server (DNS) address to
the IP address of the router or obtain the DNS
address from the network provider.
6 User Interface
.
.
.
120