Honeywell Fire-Lite Alarms MS-9050UD Manual page 169

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms MS-9050UD:
Table of Contents

Advertisement

Pressing 3 while viewing Print Screen #1 allows the user to print the detector data for each
addressable smoke detector connected to the system. A printout, similar to the following example,
will be generated if an optional printer is connected to the FACP.
DEVICE#
DEVICE TYPE
1D001
SMOKE (PHOTO)
1D002
SMOKE (PHOTO)
1D003
SMOKE (PHOTO)
1D004
SMOKE (PHOTO)
1D005
SMOKE (PHOTO)
1D006
SMOKE (PHOTO)
1D007
SMOKE (PHOTO)
1D008
SMOKE (PHOTO)
1D009
SMOKE (PHOTO)
Chamber Value
The Chamber value should be within the indicated range for the following smoke detectors:
SD350(T), SD355(T), D350P(R), SD300(T), AD350 and AD355 Addressable Photoelectric
Smoke Detectors: 405 - 2100 (obscuration of 1.00%/ft to 3.66%/ft.)
CP350, CP355 and CP300 Addressable Ionization Smoke Detectors: 750 - 2100 (obscuration
of 0.50%/ft. to 1.44%/ft.)
If the addressable smoke detector's Chamber reading is not within the acceptable range, clean the
detector and check the Chamber value again. If the reading is still not within the acceptable range,
immediately replace the detector.
Drift Compensation
Drift compensation uses software algorithms that identify and compensate for long-term changes in
the data readings from each addressable smoke detector. These long-term changes in detector data
readings are typically caused by dirt and dust accumulation inside the smoke chamber. Drift
compensation performs the following functions:
Samples each photoelectric smoke detector every 6 seconds and each ionization smoke
detector every 3 seconds
Allows a smoke detector to retain its original ability to detect actual smoke and resist false
alarms, even as dirt and dust accumulate
Reduces maintenance requirements by allowing the control panel to automatically perform
the periodic sensitivity measurements required by NFPA Standard 72
The FACP software also provides filters to remove transient noise signals, usually caused by
electrical interference.
MS-9050UD PN 52413:C 01/23/08
%DRIFT COMP
CHAMBER
20
1281
20
1281
21
1259
20
1309
21
1281
20
1322
20
1280
20
1215
20
1310
Operating Instructions
TIME/DATE
12:01AM 01-08-2001
12:01AM 01-08-2001
12:01AM 01-08-2001
12:02AM 01-08-2001
12:02AM 01-08-2001
12:02AM 01-08-2001
12:02AM 01-08-2001
12:02AM 01-08-2001
12:02AM 01-08-2001
169