Operating Instructions
Third line in display: Z000 indicates the zone programmed to this device which, in this
example, is general alarm Zone 000. Note that a single device can be programmed to five
different zones but only the first zone will be displayed.
Fourth line in display:

4.6 Supervisory Operation

Supervisory operation is similar to alarm operation but with the following differences:
The piezo sounder pulses ½ second On and ½ second Off
The Supervisory LED flashes ½ second On and ½ second Off
The LCD displays the status label Active Supervisory along with the device name, type,
address, adjective/noun, associated zones and time/date
Communicate the supervisory condition to the Central Station
The supervisory relay is activated
The alarm relay is not activated
Silenced alarms are resounded
Timers are not started
Store event in history buffer
Terminate upload or download communications
A typical Supervisory event would be displayed as illustrated in the following:
Note that, like alarms, supervisory signals latch (except when programmed for supervisory
autoresettable) and can be assigned to software zones. Supervisory alarms do not cause resound as
do other alarm conditions. Open circuits in supervisory wiring are processed by the control panel
the same way as other trouble conditions. Refer to "Alarm Operation" on page 151, for a
description of the information displayed on the control panel LCD.
152
<NOUN>; refers to the user programmed noun descriptor from library list resident in the
control panel or custom entry via PC.
Time; the current time in this example is 10:00A which represents 10:00 AM
Date; the current month, day and year in this example is 09 for September, 08 for the 8th
day of the month and 04 for the year 2004
Device Address; 1M001 in this example 1 represents SLC Loop, M represents a module
and 001 represents device address 001
ACTIVE
<ADJ> <NOUN>
10:00A 090805 1M001
SUPERVISORY
Z000
MS-9050UD PN 52413:C 01/23/08